10/19/2022 JGARCIA1 BUILDING-COMMERCIAL REVIEW Completed
10/20/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

The previous electrical plan review comments are not completely addressed to provide clear definite compliance with the following comment.

“Provide complete power and lighting floor plans showing all branch circuits, lighting controls, and panel designations for all luminaires and electrical devices, mechanical equipment”.

1 Please provide more detail on the power and lighting plans to verify the complete scope of work. For example; The luminaire schedule Plan E-1 shows 8 different types of luminaires, and the lighting floor plan only shows 3-‘A’ and 1-‘B’ type. Where are the others?

2 The power floor plan shows a Kitchen Equipment Schedule with 20+ items listed. Why is the equipment not shown on the power floor plan and branch circuit/panel designations? Not shown on the ELECTRICAL CONNECTION PLAN K-1...

3 Provide complete compliance with the 2018 IECC for the lighting.

Please revise the plans to clearly indicate this information.



Ref; 2018 IBC sec 107.1,107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.