Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T22CM06117
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/19/2022 | JGARCIA1 | BUILDING-COMMERCIAL | REVIEW | Completed | |
10/20/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comments and provide a written response. The previous electrical plan review comments are not completely addressed to provide clear definite compliance with the following comment. “Provide complete power and lighting floor plans showing all branch circuits, lighting controls, and panel designations for all luminaires and electrical devices, mechanical equipment”. 1 Please provide more detail on the power and lighting plans to verify the complete scope of work. For example; The luminaire schedule Plan E-1 shows 8 different types of luminaires, and the lighting floor plan only shows 3-‘A’ and 1-‘B’ type. Where are the others? 2 The power floor plan shows a Kitchen Equipment Schedule with 20+ items listed. Why is the equipment not shown on the power floor plan and branch circuit/panel designations? Not shown on the ELECTRICAL CONNECTION PLAN K-1... 3 Provide complete compliance with the 2018 IECC for the lighting. Please revise the plans to clearly indicate this information. Ref; 2018 IBC sec 107.1,107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. |