Permit Number: T22CM06117
Parcel: 10707016D

Address:
1380 W GRANT RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T22CM06117
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/11/2022 SCABRAL1 ENGINEERING REVIEW Passed
08/19/2022 JVINCEN1 FIRE REVIEW Approved
08/26/2022 WILDAN BUILDING-COMMERCIAL REVIEW Reqs Change Activity Number: T22CM06117 - UNIT 283

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

BUILDING REVIEW COMMENTS:
Denied
Show all new lighting on reflected ceiling plan
Show new ceiling tile layout; provide installation details

If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
08/29/2022 STEVE SHIELDS ZONING REVIEW Approved
08/29/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/30/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
08/30/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
08/30/2022 ROBERT SHERRY WATER REVIEW Passed
09/08/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

1 Provide complete power and lighting floor plans showing all branch circuits, lighting controls, and panel designations for all luminaires and electrical devices, mechanical equipment.

2 Show the locations of all new luminaires and correlate identifications of each luminaire with the luminaire schedule.

3 Provide compliance with the 2018 IECC for the lighting.

4 Provide complete panel schedules including load calculations. Indicate if new or existing.

5 If electrical load increases due to additional equipment, provide a complete electrical line diagram and total building load calculations. If there is no electrical load increase, specify this on the electrical plans.

6 Provide for GFI protected receptacles where applicable per NEC 210.8(B).

7 Provide complete compliance with the 2012 Tucson/Pima County Outdoor Lighting Code if applicable.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements, City of Tucson Outdoor Lighting Code (OLC).