Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T22CM06093
Parcel: 12913217A

Address:
2305 S PARK AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T22CM06093
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/12/2022 LEVANS2 ENGINEERING REVIEW Reqs Change The associated development package needs to be approved prior to approval of any permits.

Lianne Evans
lianne.evans@tucsonaz.gov
10/13/2022 PAUL CAMARENA ZONING REVIEW Reqs Change FROM: Paul Camarena
PDSD Zoning Review Section

PROJECT: T22CM06093
Office
2305 S PARK AV Zoning R-2

TRANSMITTAL DATE:?October 13, 2022


COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


1.COMMENT: Zoning has reviewed the building plan for compliance with DP22-0234 and although it appears that the building plans match the DP Zoning cannot approve the building plans until the DP is approved.

If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov
10/17/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM06093


GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
1. The Enercalc calculations submitted in response to the correction items have following issues which needs to be addressed:
a} Page marked 57A shows overall maximum deflection of 53.8088 inches at 15 feet location.
b} Page marked 57B shows overall maximum deflection of 54.3204 inches at 15.15 feet location.
c} Page marked 57C shows overall maximum deflection of 87.2767 inches at 18 feet location.
d} Page marked 57D shows overall maximum deflection of 89.6712 inches at 18 feet location.
Verify the Enercalc calculation pages submitted and revise as needed. These excessive deflections are beyond the allowable limits.
Submit a response letter addressing these correction items and provide bubbles on the revisions to the drawings.


BUILDING REVIEW COMMENTS:
Approved


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
1. Provide duct smoke detectors for relocated unit's ac units 8,9 and 11 over 5 ton (IMC2018,606.2.1) Complied
Approved/subject to field approval


ELECTRICAL REVIEW COMMENTS
Approved


PLUMBING REVIEW COMMENTS:
Approved


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov