Review Details: COMMERCIAL - TI

Permit Number - T22CM06030
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/30/2022 STEVE SHIELDS ZONING REVIEW Approved
08/30/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
08/30/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Clarify the scope of work. Are two bathrooms being remodeled (1st and 2nd floors) or just one? Reference: Section 107.2.1, IBC 2018.
2. Provide details to show that the construction of the shower receptors comply with the requirements of Section 421.5, IPC 2018.
3. Detail 1/A4.0 calls for each shower enclosure to have a "new linear drain" but this linear drain does appear to be included in the plumbing fixture schedule. Coordinate the architectural and plumbing designs. Reference: Section 107.2.1, IBC 2018.
08/30/2022 SSHIELD1 ENGINEERING REVIEW Passed
08/30/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/30/2022 ROBERT SHERRY WATER REVIEW Completed
09/01/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

1 Indicate or show the exhaust fan wiring and controls for 1st and 2nd floor restrooms. See mechanical plan for additional information. Also provide branch circuit information both 1st and 2nd floor restrooms.

2 Provide IECC compliance.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.
09/01/2022 JVINCEN1 FIRE REVIEW Approved
09/20/2022 WILDAN BUILDING-COMMERCIAL REVIEW Reqs Change Activity Number: T22CM06030

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

BUILDING REVIEW COMMENTS:
Denied
Sheet A1.0 Restroom shall comply with ICC A117.Provide details of accessible
restroom and showers.


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov