| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/31/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comments and provide a written response. 1 Equipment grounds and neutrals are not to be bonded together at the existing unit panels. Only at the service location, see NEC 250.6, 250.24(A)(1). Ground Diagram-E1.0 is incorrect. 2 The site plan ES1.1 shows 4 service disconnects and the One Line Drawing only shows 3. Revise the plans so they correlate with each other. 3 How are going to utilize a UFER grounding electrode on existing buildings? Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. |