08/31/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

1 Equipment grounds and neutrals are not to be bonded together at the existing unit panels. Only at the service location, see NEC 250.6, 250.24(A)(1). Ground Diagram-E1.0 is incorrect.

2 The site plan ES1.1 shows 4 service disconnects and the One Line Drawing only shows 3. Revise the plans so they correlate with each other.

3 How are going to utilize a UFER grounding electrode on existing buildings?

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.