Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T22CM05918
Parcel: 113083050

Address:
3051 N EUCLID AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T22CM05918
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/15/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
09/15/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
09/22/2022 WILDAN BUILDING-COMMERCIAL REVIEW Completed
09/28/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

1 The electrical plans are not complete. Please include the following;

Complete electrical line diagram. Include total building load.

Complete panel schedule including load calculations per NEC art 220, indicate voltage and phase, AIC and amp ratings. Balance phases as close as possible NEC 408.3(B).

Show branch circuit and panel designations for all devices, lighting, mechanical and water heater on the electric floor plan and correlate with the panel schedule.

Provide GFI protection for the new Washer receptacle. NEC 210.8(A)(10).

Provide receptacles and placement in existing unit 3053 as required per NEC art 210.52(A).

Provide tamper resistant receptacles for all new and replaced receptacles. NEC 406.12, NEC 210.

Provide compliance with NEC 210.12, 406.4(D) (Arc Fault protection) for new or replaced receptacles.

Show the location of the main electrical service for this building on the electrical plan.

Show the location of the new rooftop AC unit and provide disconnecting means and maintenance receptacle NEC 210.63.

Provide smoke detectors in corridors and sleeping areas in compliance with 2018 IBC section 907.2.10.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.