Permit Number: T22CM05918
Parcel: 113083050

Address:
3051 N EUCLID AV

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T22CM05918
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/11/2022 SCABRAL1 ENGINEERING REVIEW Passed
08/15/2022 JVINCEN1 FIRE REVIEW Approved
08/18/2022 STEVE SHIELDS ZONING REVIEW Approved
08/18/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/25/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Ventilation for kitchens in private dwellings requires a minimum of 25 CFM (continuous operation) or 100 CFM (intermittent operation) of mechanical exhaust with no recirculation of air. This may be accomplished with either a kitchen hood or an exhaust fan mounted in the kitchen. (e.g. specify the exhaust flowrate for the kitchen hood). Reference: Table 403.3.2.3, IMC 2018.
08/25/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide a plumbing design for the revised kitchen. Reference: Section 107.2.1, IBC 2018.
08/25/2022 ROBERT SHERRY WATER REVIEW Passed
08/30/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

Provide complete electrical power and lighting plans showing all electrical changes and or additional electrical and lighting that complies with the 2017 NEC.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.
09/02/2022 WILDAN BUILDING-COMMERCIAL REVIEW Reqs Change Activity Number: T22CM05918

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


Sheet 2 1. Provide details of new slab and raised curb for bedroom addition to allow for weep screed for stucco. 2. Provide details for ceiling repairs when wall is being removed, maintain the current joist spacing. 3. What type of door is replacing the window near bdrm #3?



If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov