Permit Number: T22CM05879
Parcel: 10408078B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T22CM05879
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/30/2022 LEVANS2 ENGINEERING REVIEW Reqs Change This CM cannot be approved until the associated DP, DP22-0170, is approved.

Lianne Evans
lianne.evans@tucsonaz.gov
10/11/2022 PAUL CAMARENA ZONING REVIEW Reqs Change FROM: Paul Camarena
PDSD Zoning Review Section

PROJECT: T22CM05879
New Sales building
700 W AUTO MALL DR Zoning C-3

TRANSMITTAL DATE:?October 11, 2022


COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


1.COMMENT: Zoning has reviewed the building plan for compliance with DP22-0170 ,Zoning cannot approve the building plans until the DP is approved.
If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov
10/12/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Approv-Cond Activity Number: T22CM05879

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Conditionally Approved
DEFERRED SUBMITTAL REQUIREMENTS
Structural general notes are to include any components of the building that may be considered deferred submittals. IBC Section 107.3.4.1 requires deferred submittals to be approved by the building official.
If items will be deferred the plans are to clearly note the following per IBC Section 107.3.4.1:
* To be reviewed by design professional in responsible charge.
* Design professional shall affix a notation that the deferred items are in general conformance with their design of the building.
* They shall be submitted for review by the building official.
* Shall not be installed until approved by building official.
NOTE: Every effort has been made to identify the code violations. Any oversight by the review team shall not be considered an authority to violate, set aside, cancel or alter applicable codes or ordinances. The plan review and permit issuance shall not be considered a warranty or guarantee. The Structural Engineer is responsible for following ALL applicable Federal, State and local Municipal Codes and Ordinances.


BUILDING REVIEW COMMENTS:
Approved


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
all corrections complied
Approved/subject to field approval


ELECTRICAL REVIEW COMMENTS
Conditionally Approved
E103 ELECTRICAL POWER PLAN: Could not locate Keynote #31.
E301 ELECTRICAL HVAC PLAN: Reference to Keyed Notes on Sheet E304 doesn’t seem accurate. Comment applies to other sheets.
ES1.0 ELECTRICAL SITE PLAN: The EOR should have performed an estimated lumens per acre calculation to prove compliance with Tucson city requirements.


PLUMBING REVIEW COMMENTS:
Approved
Second Plumbing Review= OK Subject to Field Inspections
1 thru 3 OK


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov