Permit Number: T22CM05879
Parcel: 10408078B

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T22CM05879
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/15/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM05879

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Conditionally Approved
DEFERRED SUBMITTAL REQUIREMENTS
Structural general notes are to include any components of the building that may be considered deferred submittals. IBC Section 107.3.4.1 requires deferred submittals to be approved by the building official.
If items will be deferred the plans are to clearly note the following per IBC Section 107.3.4.1:
* To be reviewed by design professional in responsible charge.
* Design professional shall affix a notation that the deferred items are in general conformance with their design of the building.
* They shall be submitted for review by the building official.
* Shall not be installed until approved by building official.
NOTE: Every effort has been made to identify the code violations. Any oversight by the review team shall not be considered an authority to violate, set aside, cancel or alter applicable codes or ordinances. The plan review and permit issuance shall not be considered a warranty or guarantee. The Structural Engineer is responsible for following ALL applicable Federal, State and local Municipal Codes and Ordinances.


BUILDING REVIEW COMMENTS:
Approved


MECHANICAL REVIEW COMMENTS:
Denied
1. Appliances shall not be closer than a minimum of 10' of roof edge without approved protection (IMC2018,304.11) sheet A120
2. Repair garage requires .75 cfm per square foot of space, so you are required to provide .75 cfm times 1,719 square foot of repair garage area equals 1,289 cfm's continuously sheet M201 (IMC2018,403.3.1.1)


ELECTRICAL REVIEW COMMENTS
Conditionally Approved
E103 ELECTRICAL POWER PLAN: Could not locate Keynote #31.
E301 ELECTRICAL HVAC PLAN: Reference to Keyed Notes on Sheet E304 doesn’t seem accurate. Comment applies to other sheets.
ES1.0 ELECTRICAL SITE PLAN: The EOR should have performed an estimated lumens per acre calculation to prove compliance with Tucson city requirements.


PLUMBING REVIEW COMMENTS:
Denied
First Plan Review:
1). The 4" horizontal roof conductors for the 172 GPM roof drains are undersized on plan page P101 or need to have pitch shown as 1/2" slope -IPC 1106.2
2). The 4" horizontal roof conductors for the 153 GPM roof drains are undersized on plan page P101 or need to have pitch shown as 1/4" slope -IPC 1106.2
3). Floor drain vent details #4 & #5 on P301 sanitary vents can't be routed horizontally below floor over to wall before becoming vertical. Vent rise needs to comply with-IPC 905.3, 905.4 or ( suggest combination drain & vent system) Update P301 & P101.


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
08/16/2022 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: T22CM05879 – DP22-0170
700 W Auto Mall Dr – C-3
New Auto Sales Building – (1st Review)

TRANSMITTAL: August 16, 2022

This site is located in C-3 Zone (UDC Article 4.7.22). Auto sales is a permitted use (UDC Table 4.8-4), subject to Use Specific Standards 4.9.9.G.1& .2.

1. As DP22-0170 has not completed the first review Zoning is not able to compare the building plans to the DP. Once the 1st review of the DP is completed and comments addressed Zoning will review the building plans for compliance with the DP. Additional comments maybe forth coming. Zoning cannot approve the building plans until the DP is approved by all review agencies.

2. Based on the sheet index it appears you are proposing to include the development package sheets in the building plan set. If you include the DP sheets they either need to be the stamped approved DP sheets or marked for reference only.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
08/16/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
08/22/2022 JVINCEN1 FIRE REVIEW Approved
08/30/2022 ROBERT SHERRY WATER REVIEW Completed
09/08/2022 SBLOOD1 ENGINEERING REVIEW Reqs Change The DP needs to be approved before the building plans can be approved.

Stephen Blood
(520) 837-4958
Stephen.blood@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
09/08/2022 VVERA1 OUT TO CUSTOMER Completed