Review Status: Completed
Review Details: CELL TOWER/ANTENNAS
Permit Number - T22CM05868
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/03/2022 | PSHELTO1 | FIRE | REVIEW | Approved | |
| 08/10/2022 | SCABRAL1 | ENGINEERING | REVIEW | Passed | |
| 08/18/2022 | PETER MCLAUGHLIN | PLANNING-CITY HALL | REVIEW | Approved | |
| 08/18/2022 | PETER MCLAUGHLIN | ZONING | REVIEW | Completed | |
| 08/29/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comments and provide a written response. Ref; Plan Sheet E-1, Line Diagram Indicate the rating of the OCPD in the generator. Also, what does the encircled G represent? Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. |
| 09/01/2022 | WILDAN | BUILDING-COMMERCIAL | REVIEW | Completed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/01/2022 | VVERA1 | OUT TO CUSTOMER | Completed |