Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T22CM05845
Parcel: 13215005B

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T22CM05845
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/12/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
08/12/2022 STEVE SHIELDS ZONING REVIEW Denied ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T22CM05845
710 E Evans Blv. – I-1 (1st Review)

TRANSMITTAL: August 12, 2022
This site is located in I-1 Zone (UDC 4.7.29).

1. Per UDC Article 3.3.3.G.2.c A site plan (Development Package) is required for the following types of development: Existing development undergoing a change of use, building structure additions, and/or a reconfiguration of an area outside a building. A development package (DP) meeting the requirements of Administrative Manual (AM) 2-06 must be submitted and approved prior to approval of this building plan. The DP is a separate submittal from the building plans and is submitted at: https://docs.tucsonaz.gov/Forms/tucsonpermitapp, using Submission Type “Site Review”.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
08/19/2022 WILDAN BUILDING-COMMERCIAL REVIEW Reqs Change Activity Number: T22CM05845

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

1. A0 602.1 Please specify the construction type of the building such as VB per this section and number of occupant- see table 1004.5.

2. 107, 1603,1604 Please submit 100 percent complete metal building and foundation plans and structural calculations for the project sealed by an engineer licensed in AZ. You must submit a letter from the City of Tucson allowing these to be deferred.

3. 1705 Please list all special inspection items for the project. Note if they are continuous or periodic.

4. 107 Please submit soils report if any is used.

5. 1705 Please submit a completed special inspection form for the project

6. 1104.2 Please identify the accessible route to the existing building and to the public way.




If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
08/23/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

1 The loads calculated for both panels' ‘B’ and ‘C’ (166 amps) together, do not correlate with the total loads shown for panel ‘A’ (145 amps), which feeds both of these panels and possible other loads. Revise and show load calculations and a complete panel schedule for panel ‘A’, also show total load for the 400-amp electrical service that complies with NEC art 220.

2 Provide and show available fault current values and AIC ratings at the electrical service and ratings for downstream panels.

3 Show the location of the existing electrical service and the new panel ‘C’ on the electrical plans. Also indicate what is existing and what is new.

4 Indicate all conductor sizes, quantities, including equipment ground for the panel ‘C’ feeders. Also the #4 Cu AWG conductors are undersized for the 200-amp OCPD in panel ‘A’ protecting the feeder and panel ‘C’. NEC 240.4, 310.15(B)(16).

5 The 150-amp OCPD in panel ‘A’ is oversized for the #3 Cu conductors feeding panel ‘B’. NEC 240.4, 310.15(B)(16)

6 The branch circuit numbers shown for the exterior receptacles located at ‘AC1’ and ‘AC2’, do not correlate with the panel schedule for panel ‘C’. NEC art 408.4.

7 Provide disconnecting means and show circuit and panel designations on the power plan for the Mechanical equipment.

8 Provide for a complete grounding electrode system for the new building as required per NEC art 250.32.

9 Provide complete compliance with the 2012 Tucson/Pima County Outdoor Lighting Code (OLC) for the exterior lighting. Provide plans and evidence on the plans that the proposed exterior lighting fully complies with the Outdoor Lighting Code. See section 104 for plan submittal requirements.

(a)Provide site lighting plans with the following information on the plans;

(b) Size of the parcel in acres.

(c) See table 401.1, lighting area and option and indicate this information in the lighting site plan, also showing the locations and types of all exterior luminaires including existing.

(d) 402.1 (light source color temperature requirements), shielding requirements, etc .

(e) Provide calculations for total lumens allowed and total lumens proposed per acre including existing lighting, for both Full Cut Off and Unshielded lighting per table 401.1.

(f) Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2.

(g) Specify any exceptions used.

(h) Curfew lighting controls If applicable.

Do not confuse the Outdoor Lighting Code with the IECC.

10 Revise the lighting Energy calculations per the 2018 IECC to comply with Table C405.3.2(1), Warehouse = .48 watts per sq.ft. Not .96. Plan Sheet A0 refers to the new building as “WAREHOUSE”.

11 Provide and indicate lighting controls for the exterior lighting.

12 Provide a complete luminaire schedule for all luminaires, and also correlate the exterior luminaires with the exterior lumen calculations.

13 Ref; Electrical Specifications “GENERAL” Notes. Revise the 2018 NEC reference to 2017 NEC.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. 2012 Tucson/Pima County Outdoor Lighting Code (OLC).
08/29/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Show the path of travel and the distance from the new warehouse to the toilet facilities. Reference: Section 2902.3.3, IBC 2018.
08/29/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Demonstrate energy code compliance for the building envelope using calculations based on the current code (e.g. COMcheck Envelope Compliance Certificate). Reference: Sections C101.5, C103.2, C303, and C401.2, International Energy Conservation Code 2018.
2. Show that the proposed HVAC equipment meets the minimum performance requirements of Section C403.3.2, IECC 2018.
3. Full compliance with the 2018 IECC for new buildings requires that an "additional efficiency package option" be selected per Section C406. Identify which of the eight options has been selected. Reference: Section C401.2 (2), IECC 2018.
4. Show the size, routing, and termination of the condensate drains. Reference: Section 307.2.1, IMC 2018 as amended by the City of Tucson.
5. Secure the refrigerant circuit access ports of the heat pumps to prevent unauthorized access. Reference: Section 1101.10, IMC 2018.
08/29/2022 ROBERT SHERRY WATER REVIEW Passed
09/08/2022 JVINCEN1 FIRE REVIEW Approved
09/12/2022 SBLOOD1 ENGINEERING REVIEW Reqs Change See zoning comment for need of a Development Package submittal.

Stephen Blood
(520) 837-4958
Stephen.blood@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
09/12/2022 NGARCIA3 OUT TO CUSTOMER Completed