Permit Number: T22CM05833
Parcel: 137055230

Review Status: Completed

Review Details: OTHER

Permit Number - T22CM05833
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/22/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that the Registrant's seal shall have both a signature of the registrant and the date the document was sealed.
2. Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1 and C502.2.3, IECC 2018.
08/24/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
08/31/2022 WILDAN BUILDING-COMMERCIAL REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
08/31/2022 VVERA1 OUT TO CUSTOMER Completed