Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T22CM05832
Parcel: 137055220

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T22CM05832
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/12/2022 STEVE SHIELDS ZONING REVIEW Approved
08/12/2022 SSHIELD1 ENGINEERING REVIEW Passed
08/12/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/19/2022 JVINCEN1 FIRE REVIEW Approved
08/19/2022 WILDAN BUILDING-COMMERCIAL REVIEW Reqs Change Activity Number: T22CM05832

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

Sheets A602 & A911 are missing from plans.



If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
08/23/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Revise the sequence of operation for the restroom exhaust fans so that all of the air supplied to the restrooms will be exhausted (i.e. all of the air supplied to each restroom is to be exhausted during the hours of operation even if the lights are off). The exhausted air from the restrooms shall be limited to no more than 10% of any subsequent supply air stream. Reference: Section 403.2.1 (4), IMC 2018.
2. Calculation of the required minimum ventilation for an air handler serving multiple zones requires the balancing data (supply CFM) for each zone and the calculations described in Sections 403.3.1.1.2.3.1 through 403.3.1.1.2.3.4, IMC 2018. Include the area air flow rate (CFM per square foot) as well as the occupant air flow rate (CFM per occupant). Reference: Section 403.3.1.1.2.3, IMC 2018.
3. Coordinate the OSA flow rates shown in the OSA calculations, the rooftop unit schedule, and the air balance schedule. Note: It is physically impossible to have 700 CFM of OSA plus 2300 CFM of return air entering a RTU with only 2000 CFM of supply air. Reference: Section 107.2.1, IBC 2018.
4. The outside air and make-up airflow rates significantly exceed the exhaust airflow rates. Show how over-pressurization of the building will be avoided. Reference: Section 501.4, IMC 2018
5. The mechanical plan shows high velocity diffusers for the make-up air system in close proximity to the face of the Type I hoods. Verify that the location and type of make-up air outlets complies with the hood manufacturer's installation instructions and does not reduce the effectiveness of the exhaust system. Reference: Sections 304.1 and 508.1, IMC 2018.
6. Verify that the evaporative cooling section of the makeup air unit is equipped with a recirculating water system. Reference: Section 928.2, IMC 2018 and ARS Title 45, Chapter 1, Article 12. See text at: (http://www.azleg.gov/viewdocument/?docName=http://www.azleg.gov/ars/45/00313.htm)
08/23/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Verify that the Pima County Regional Wastewater Reclamation Department will allow the drain from the prep sink to bypass the grease interceptor. Reference: Section 1003.3, IPC 2018, as amended by the City of Tucson.
08/23/2022 ROBERT SHERRY WATER REVIEW Completed
08/24/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

1 Provide for GFI protected receptacles in the kitched and food prep areas as required per NEC art 210.8B(2).

2 Provide a luminaire schedule.

3 Provide compliance with the 2018 IECC for the lighting.

4 Provide power and wiring for the Hood, Exhaust Fan. Show locations and power home runs on the power plan.

5 Revise the reference to the 2019 NEC to the current adopted 2017 NEC in the General Notes.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.