Review Date Reviewer's Name Type of Review Description Status Comments
08/04/2022 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change Provide a complete plan set showing 2018 IRC compliance including a wall and foundation detail showing materials, locations, sizing and fastening, electrical, plumbing, heating cooling, insulation placement and attic space venting.
08/08/2022 SCABRAL1 ENGINEERING REVIEW Passed
08/09/2022 JVINCEN1 FIRE REVIEW Approved
08/11/2022 PAUL CAMARENA ZONING REVIEW Reqs Change FROM: Paul Camarena
PDSD Zoning Review Section

PROJECT: T22CM05813
Addition
333 N WILSON AV
Zoning R-1

TRANSMITTAL DATE:?August 11, 2022


COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


1.COMMENT: The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure’s wall facing each interior property line (Table 6.3-2.A). Based on a wall height of 14’-4” the required perimeter yard setback from the proposed addition to the north property line is 9’-7”, proposed setback is 6’-10”. A Design Development Option (DDO) must be submitted and approved to reduce the required setback, Based on a wall height of 14’-4” the required perimeter yard setback from the proposed addition to the south property line is 9’-7”, proposed setback is 6’-8”. A Design Development Option (DDO) must be submitted and approved to reduce the required setback,

DDO application and requirements can be found at: https://www.tucsonaz.gov/files/pdsd/forms/DDO_for_Setback_and_Height_UDC_8.11.20.pdf. A DDO is a separate submittal from the building plan and shall be submitted at: https://www.tucsonaz.gov/pdsd-filedrop, using the Submission Type “Zoning Administration”. If you have questions about the DDO application or process please contact Mark Castro at Mark.Castro@tucsonaz.gov

2.COMMENT: The Pima County Assessor’s effective construction date for your building or structure is 1948. The actual construction date may be earlier.
Buildings, portions of buildings or structures that are 50 years of age or older must be architecturally documented prior to demolition. Documentation will be reviewed and approved by the Historic Preservation Office before a permit is issued.
Demolition (Historic and Older Structures) Application and General Information may be downloaded (PDF) at https://www.tucsonaz.gov/pdsd/all-application-forms-submittal-requirements
Return completed documentation to PDSDHistoric@tucsonaz.gov. Applicant will be contacted within 5 working days if additional materials are required for review.

3.COMMENT: Draw dimension and label the height of the new structure measured from design grade to top of wall.

4.COMMENT: Clearly show everything on site. Clarify if the existing metal structure to the northwest is to be removed additional comments may be forthcoming
5.COMMENT: Show parking per UseSpecific Standards 4.9.7.B.7 which states “ For any new single-family dwelling in the R-1 zone with five bedrooms , three parking spaces are required.For every bedroom over five, one additional space is required for each bedroom . For all single-family dwellings in the R-1 zone with five or more bedrooms , and for all lots containing two or more single-family dwellings, with the second dwelling having more than one bedroom , all parking spaces must be located on-site , either in a side or rear perimeter yard . Parking spaces may not be located in a vehicular use area in any front street perimeter yard . A parking area is not required to be developed to a commercial standard. A dustproof parking surface is required to at least a minimum of two inches of compacted pea gravel. An existing covered residential parking area may be used.

If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov
08/26/2022 AWARNER1 NPPO REVIEW Approved