Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T22CM05772
Parcel: 128100810

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T22CM05772
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/09/2022 SSHIELD1 ENGINEERING REVIEW Passed
08/09/2022 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T22CM05772
5420 E Broadway Blvd, Suite 260 – PAD-1
TI Food Service (1st Review)

TRANSMITTAL: August 9, 2022
This site is located the PAD-1, Food Service use is an allowed use in the PAD.

1. Provide a approved permit documents that approved the outdoor seating shown on the plan. If you are unable to provide approved documents per UDC Article 3.3.3.G.2.c A site plan (Development Package) is required for the following types of development: Existing development undergoing a change of use, building structure additions, and/or a reconfiguration of an area outside a building. A development package (DP) meeting the requirements of Administrative Manual (AM) 2-06 must be submitted and approved prior to approval of this building plan. The DP is a separate submittal from the building plans and is submitted at: https://docs.tucsonaz.gov/Forms/tucsonpermitapp, using Submission Type “Site Review”.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
08/09/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/13/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM05772

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Denied
1. Update the sheet index on sheet A000 to include all drawings or provide separate indexes for each discipline. Only the architectural plans are listed.


MECHANICAL REVIEW COMMENTS:
Denied
1. Provide a mechanical COMcheck or other approved methodology for the project for the new proposed mechanical units. 2018 IECC C403.1.1.
2. Update the floor plans to indicate the existing back door that is being infilled in accordance with the architectural plans.


ELECTRICAL REVIEW COMMENTS
Denied
1. Indicate the location of an existing emergency light outside of both east side exits or indicate a new fixture will be installed. Only the north and south are indicated as having EM exterior fixtures. 2018 IBC 1008.3.2.
2. Update the floor plans to indicate the existing back door that is being infilled in accordance with the architectural plans.


PLUMBING REVIEW COMMENTS:
Denied
1. The plans indicate the location of a new hot water heater above the existing cooler. Clarify if this is an additional water heater or if the existing water heater is being relocated. Provide additional information on the required plumbing, gas, venting and safety requirements on the drawings.


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
08/15/2022 JVINCEN1 FIRE REVIEW Approved
08/29/2022 ROBERT SHERRY WATER REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
08/29/2022 NGARCIA3 OUT TO CUSTOMER Completed