Permit Number: T22CM05741
Parcel: 135083470

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T22CM05741
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/02/2022 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change Provide a site plan showing the location of the electrical service panel and any sub panels. Include the feeder size to the shed.

Provide a floor plan showing the location of all switch, light and receptacle outlets.
08/03/2022 SBLOOD1 ENGINEERING REVIEW Passed
08/12/2022 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL
FROM: PDSD Zoning Review
PROJECT: T22CM05741
1808 S Prudence Rd – R-1
Detached Shed w/electrical (1st Review)

TRANSMITTAL DATE: August 12, 2022
Provided a detail comment response letter with your submittal that clearly shows how you have addressed all comments with your next submittal.
This site is located in the R-1 zone (UDC 4.7.8). A single-family residence is a permitted use in this zone (Table 4.8-2) subject to Use Specific Standards 4.9.7.B.5 – 9.
1. Provide a residential plot plan that meets all the requirements found at: https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf, to include but not limited to:
a. Owner name on the plot plan
b. Provide a lot coverage calculation that meets the requirements of UDC Article 6.4.3 and the example shown on the Residential Plot Plan Requirements.
c. Clearly show all structures, sheds, ramadas, etc. on the plan and include them in the lot coverage.
d. Provide the height of the exterior wall for the new building.
e. Show the location of all utility lines on the plan.
f. Provide the zoning of the property and all adjacent properties.
g. Provide the legal description “MANANA GRANDE C LOT 339” on the plot plan.

2. The parcel dimension shown on the plan are not correct. Review final plat Manana Grande “C” found at: https://www.tucsonaz.gov/apps/maps-and-records/subdivisions/search?book=16&pg=029, and provide the correct property dimensions.

3. Provide a black & white plot plan as the light blue colors are difficult to read.

4. It is not clear which structure is being permitted.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
08/26/2022 AWARNER1 NPPO REVIEW Approved