Permit Number: T22CM05695
Parcel: 105110690

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T22CM05695
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/26/2022 VFLORES1 PIMA COUNTY - ADDRESSING PIMA COUNTY - ADDRESSING Reqs Change Please contact Pima County Addressing to have all unit # added into the system Phone #:520-724-9512 Email: addressing@pima.gov
08/04/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM05695

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
1. Provide structural calculations for the modifications of the roof structure for the new HVAC unit.

BUILDING REVIEW COMMENTS:
Denied
1. Sheet TS1: The construction type provided is not a recognized construction type by the IBC. It is assumed that Type V-B is desired and will be reviewed as such. Provide a corrected construction type.
2. Sheet TS1: The incorrect edition of the NEC is provided. Provide the correct edition of the NEC that is adopted and enforced by the City of Tucson.
3. Sheet A2.0: The occupant load is not calculated for the reception or the gym area. This is an assembly space and should be accounted for appropriately. Provided a corrected occupant load calculation in accordance with Section 1004.3 and Table 1004.5.
4. Sheet A2.0: The egress plan does not provide any travel distance measurements. Provide all travel distance measurements.
5. Sheet A2.0: Provide clarification on the adjacent tenants as additional fire separation may be required.
6. Sheet A2.0: Based on measurements taken; the mop sink is in the clear floor space of the water closet. Provide the appropriate clear floor space in accordance with Section 604.3.1 and 604.3.2 of ADAAG.
7. Sheet A2.0: It appears that egress and accessibility will be heavily impeded by the work out equipment. Clearly indicate the egress and accessible routes that are not impeded by equipment in accordance with Section 1005.3.2, 1005.4 and ADAAG.

MECHANICAL REVIEW COMMENTS:
Approved

ELECTRICAL REVIEW COMMENTS
Approved

PLUMBING REVIEW COMMENTS:
Approved


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
08/09/2022 SSHIELD1 ENGINEERING REVIEW Passed
08/09/2022 STEVE SHIELDS ZONING REVIEW Approved
08/09/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/19/2022 JVINCEN1 FIRE REVIEW Reqs Change -Resolve building comments
-Top right of sheet TS1 list the town of Marana in the address.

john.vincent@tucsonaz.gov
5203495581
08/25/2022 ROBERT SHERRY WATER REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
08/25/2022 VVERA1 OUT TO CUSTOMER Completed