Permit Number: T22CM05694
Parcel: 12702278B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T22CM05694
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/09/2022 WBERGER1 ZONING REVIEW Approved
08/09/2022 WBERGER1 ENGINEERING REVIEW Passed
08/09/2022 WBERGER1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/18/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
08/18/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

1 Ref; Plan Sheet E2.0.

Show the luminaire switching controls and new switching for the Barber Shop. See Keynote #2.

Re f; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.
08/18/2022 JVINCEN1 FIRE REVIEW Approved
08/18/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
08/18/2022 ROBERT SHERRY WATER REVIEW Reqs Change Provide the size of the water meter serving this suite, the size of the backflow preventer associated with the water meter, and the total water demand served by the water meter. Reference: Section 107.2.1, IBC 2018.
08/19/2022 WILDAN BUILDING-COMMERCIAL REVIEW Reqs Change Activity Number: T22CM05694

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

The maneuvering clearance required for Latch approach, Pull side is 48", if a closer is installed, 54" min. is required. ICC A117.1


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov