Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T22CM05693
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/26/2022 | VFLORES1 | PIMA COUNTY - ADDRESSING | PIMA COUNTY - ADDRESSING | Reqs Change | Please contact Pima County Addressing to have Building #2 added into the system Phone #:520-724-9512 Email: addressing@pima.gov |
| 08/01/2022 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Reqs Change | Activity Number: T22CM05693 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Denied Sheet F1 - Provide list of deferred submittals. Special inspection documentation – Provide statement and schedule of special inspections per 2018 International Building Code. Cross reference all the details in 6 of 8, 7 of 8, and 8 of 8 sheets in foundation plan and framing plans. BUILDING REVIEW COMMENTS: Denied Architect stamp/seal/date – Architect stamps are dates “12/16/16” so provide architect stamp that is up to date. Arizona state board of technical registration shows Mr. Michael Anderson / 61160 has expired 31 December 2021 and delinquent. Please provide active AZ registered professional stamp/sign/seal. Sheet G101 – Provide detailed description of work. Sheet G101 – Select and provide complete list of building codes that are applicable to this project. City of Tucson IBC Local Amendments • Amendments to the 2018 International Building Code • Amendments to the 2018 International Existing Building Code • Amendments to the 2018 International Energy Conservation Code • Amendments to the 2018 International Fuel Gas Code • Amendments to the 2018 International Mechanical Code • Amendments to the 2018 International Plumbing Code • Amendments to the 2018 International Residential Code • Amendments to the 2018 International Swimming Pool & Spa Code • Amendments to the 2017 National Electrical Code • Amendments to the 2018 International Fire Code • City of Tucson/Pima County Outdoor Lighting Code • Arizona Administrative Code Title 18 Chapter 5 for public and semi-public swimming pools • ICC A117.1 - 2009 Accessible and Usable Buildings and Facilities (by reference) Adopting Local Amendments to the Building Code is authorized by Ordinance #11590. Sheet G101 – Provide complete building code analysis per 2018 International Building Code for this permit i.e. climatized RV Storage Building. Does it have sprinkler system and fire alarm system? Is it S-1 or S-2 occupancy? What is the total building area? Business area is specified while none showed in floor plan. Show code analysis pertaining to this permit only. Sheet G101 – Provide legible life safety plan. Provide 1”=40’-0” is too small to read. Label the space and identify. 2018 International Building Code section 1010.1.2 egress doors shall be of the pivoted or side-hinged swing type. Sheet G101 – Automatic sprinkler system shall be provided containing a Group S-1 occupancy per 2018 International Fire Code section 903.2.9 where fire area exceeds 12,000 SF (item 1). Sheet A101 shows 21,896 SF of building square. What is the fire area (SF) per defined in 2018 International Building Code? Sheet A101 – Label the building space function. Are they climatize RV storage 101, 102? Any exterior signage? Sheet A101 – Reference note 3 identifies “LIGHT GAUGE STUD STEEL COLUMNS” while it’s tags a wall. Identify the wall and column separately. Sheet A200 – Show gutter and downspout locations coordinated with 16/7 of 8 low eave detail. Sheet A200 – Show exterior lighting coordinate with electrical lighting. MECHANICAL REVIEW COMMENTS: Denied Sheet G100 – Mechanical engineer missing for this “climatized” RV storage. Provide heating/cooling load calculations. Provide mechanical system drawings, equipment schedules, and COMchecks for this climatized RV storage building. Provide mechanical ventilation per 2018 International Mechanical Code section 403. Provide required outdoor CFM per section 403.2 including ventilation calculation. Provide mechanical exhaust per 2018 International Mechanical Code section 501. Ventilation systems shall be balanced by individuals holding current certification from the Associated Air Balance Council (AABC), the National Environmental Balancing Bureau (NEBB) or other approved agencies. Final reports shall be provided to the engineer of record and the code official prior to the issuance of certificate of occupancy per City of Tucson Amendments to the 2018 International Mechanical Code. Sheet E003 – Equipment schedule lists heat pump, air handler, exhaust fans and fan coils while missing mechanical plans. ELECTRICAL REVIEW COMMENTS Denied E001 – Sheet index lists 28 electrical sheets while 14 electrical sheets were submitted. Please provide complete electrical sheets coordinated with sheet index. E003 – Equipment schedule specifies elevators while they are not shown in plan. Please clarify this scope and coordinated with Architectural and Mechanical drawings. Clarify scope of work. E100 – Drawings overlaps title blocks. Please clarify the drawings for legibility. Provide light budget calculations compliance with the 2018 IECC for lighting and PC/COT Outdoor Lighting Code. PLUMBING REVIEW COMMENTS: Denied Sheet G100 – Plumbing engineer missing for this “climatized” RV storage. Provide plumbing plans, plumbing fixture schedule and site utility plan. Provide minimum number of plumbing fixtures per 2018 International Plumbing Code section 403. Reference table 403.1 minimum number of required plumbing fixtures – Water closets for male/female, Lavatories for male/female, drinking fountain and other/service sink. Show required and provided fixture counts. Show path of travel to shared facility if applicable. Provide size of storm drain piping per 2018 International Plumbing Code section 1106.2 and roof gutter size per section 1106.6. Provide roof gutter and downspout details accordingly. If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |
| 08/09/2022 | PAUL CAMARENA | ZONING | REVIEW | Reqs Change | REVIEW TRANSMITTAL FROM: Paul Camarena PDSD Zoning Review Section PROJECT: T22CM05693 Storage building (1st Review) 6131 E BENSON HY Zoning C-2 TRANSMITTAL: August 9, 2022 1. Zoning has reviewed the building plans for compliance with the associated unapproved Development Package DP22-0189. Zoning cannot approve the building plans until the DP is approved. If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov |
| 08/09/2022 | PCAMARE1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 08/19/2022 | JVINCEN1 | FIRE | REVIEW | Reqs Change | Resolve building comments john.vincent@tucsonaz.gov 5203495581 |
| 08/25/2022 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 09/06/2022 | SHASEMA1 | ENGINEERING | REVIEW | Reqs Change | Engineering cannot approve building permit until associated DP22-0189 has been approved Scott Haseman scott.haseman@tucsonaz.gov |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/06/2022 | VVERA1 | OUT TO CUSTOMER | Completed |