Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T22CM05691
Parcel: 110151100

Review Status: Completed

Review Details: OTHER

Permit Number - T22CM05691
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/01/2022 GSLEIGH1 OIP REVIEW Reqs Change Gas line undersized, 3/4 inch gas line cannot provide 200k BTU/hr at lengths beyond 20 feet. Please ref. 2018 IRC - Table G2413.4(1) for length/capacity table.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/01/2022 NGARCIA3 OUT TO CUSTOMER Completed