Permit Number: T22CM05672
Parcel: 10601229G

Address:
3637 N 1ST AV

Review Status: Completed

Review Details: 3RD PARTY REVIEW - COMMERCIAL

Permit Number - T22CM05672
Review Name: 3RD PARTY REVIEW - COMMERCIAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/09/2022 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: T22CM05672 – DP22-0154
3637 N 1st Ave. – C-2
New Warehouse Building – (1st Review)

TRANSMITTAL: August 9, 2022

This site is located in C-2 Zone (UDC Article 4.7.21) Commercial Storage is a permited use in the zone (UDC Table 4.8-4), subject to Use Specific Standard 4.9.10.A.

1. As DP22-0154 has not completed the first review Zoning is not able to compare the building plans to the DP. Once the 1st review of the DP is completed and comments addressed Zoning will review the building plans for compliance with the DP. Additional comments maybe forth coming. Zoning cannot approve the building plans until the DP is approved by all review agencies.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
08/09/2022 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
08/24/2022 ROBERT SHERRY WATER REVIEW Reqs Change Provide sufficient information to show that the installation of the new plumbing fixtures will not cause the existing water service and water meter to become overloaded. Reference: Section 107.2.1, IBC 2018.
09/07/2022 SBLOOD1 ENGINEERING REVIEW Reqs Change The DP needs to be approved before the building plans can be approved.

Stephen Blood
(520) 837-4958
Stephen.blood@tucsonaz.gov
09/21/2022 JPEELDA1 FIRE REVIEW Approved
09/22/2022 STANTEC 3RD PARTY REVIEW-COMMERCIAL REVIEW Completed
09/22/2022 DBENOIT1 3RD PARTY REVIEW-COMMERCIAL AT 3RD PARTY OFFICE Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
09/22/2022 VVERA1 OUT TO CUSTOMER Completed