Permit Number: T22CM05671
Parcel: 13312006G

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T22CM05671
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/09/2022 STEVE SHIELDS ZONING REVIEW Approved
08/09/2022 SSHIELD1 ENGINEERING REVIEW Passed
08/09/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/10/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
08/10/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
08/10/2022 ROBERT SHERRY WATER REVIEW Completed
08/18/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

Show the location of the restroom lighting switches or controls on the power and lighting plans.

Provide GFI protection for receptacles located within 6’ of a sink. NEC 210

Re f; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.
08/19/2022 JVINCEN1 FIRE REVIEW Reqs Change -Indicate that a fire alarm system with occupant notification will be installed per IFC 907.2.6. Also indicate it will be a deferred submittal.
09/01/2022 WILDAN BUILDING-COMMERCIAL REVIEW Completed