Permit Number: T22CM05654
Parcel: 11108183B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T22CM05654
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/12/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

Provide 150 amp fuses in the 200 amp AC disconnect to provide coordination with the 150 amp rated main breaker in the service panel feeding it. NEC 240.12.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.