Permit Number: T22CM05609
Parcel: 12701005D

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T22CM05609
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/05/2022 WBERGER1 ZONING REVIEW Approved
08/05/2022 WBERGER1 ENGINEERING REVIEW Passed
08/05/2022 WBERGER1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/15/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
08/15/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Revise detail 204 (ejector pump) to provide a full-open valve on the discharge side of the internal check valve. Reference: Sections 303.2 and 712.2, IPC 2018.
08/15/2022 ROBERT SHERRY WATER REVIEW Completed
08/16/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comment and provide a written response.
1. Provide additional wall receptacle outlets in the conference room as required per NEC 210.71B.
Ref; 2018 IBC sec 107.2.1, 2017 NEC
08/18/2022 JVINCEN1 FIRE REVIEW Approved
08/25/2022 WILDAN BUILDING-COMMERCIAL REVIEW Completed