Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T22CM05609
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/05/2022 | WBERGER1 | ZONING | REVIEW | Approved | |
08/05/2022 | WBERGER1 | ENGINEERING | REVIEW | Passed | |
08/05/2022 | WBERGER1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
08/15/2022 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
08/15/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Revise detail 204 (ejector pump) to provide a full-open valve on the discharge side of the internal check valve. Reference: Sections 303.2 and 712.2, IPC 2018. |
08/15/2022 | ROBERT SHERRY | WATER | REVIEW | Completed | |
08/16/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comment and provide a written response. 1. Provide additional wall receptacle outlets in the conference room as required per NEC 210.71B. Ref; 2018 IBC sec 107.2.1, 2017 NEC |
08/18/2022 | JVINCEN1 | FIRE | REVIEW | Approved | |
08/25/2022 | WILDAN | BUILDING-COMMERCIAL | REVIEW | Completed |