Review Details: 3RD PARTY REVIEW - COMMERCIAL TI

Permit Number - T22CM05608
Review Name: 3RD PARTY REVIEW - COMMERCIAL TI
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
07/22/2022 STANTEC 3RD PARTY REVIEW-COMMERCIAL REVIEW RECEIVED
07/22/2022 ANY 3RD PARTY REVIEW-COMMERCIAL AT 3RD PARTY OFFICE Active
08/09/2022 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
08/09/2022 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T22CM05608 – DP21-0141
865 E University Bl – HC-3
Food Service (1st Review)

TRANSMITTAL: August 9, 2022
This site is located in HC-3 Zone (UDC 4.7.22). Food Service is an allowed use in the zone (UDC Table 4.8-4).

1. Zoning has reviewed the building plans for compliance with DP21-0141 and all though it appears that the plans are in compliance until the DP is approved by all review agencies Zoning cannot approve the building plans.

2. Until the Main Gate & Historic reviews are complete Zoning cannot approve this plan.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
08/09/2022 ANY DESIGN EXAMINER REVIEW Active
08/23/2022 ROBERT SHERRY WATER REVIEW Completed
09/06/2022 SBLOOD1 ENGINEERING REVIEW Reqs Change The DP needs to be approved before the building plans can be approved.

Stephen Blood
(520) 837-4958
Stephen.blood@tucsonaz.gov
09/21/2022 JPEELDA1 FIRE REVIEW Reqs Change Sheet XI shows information for fire sprinklers and references NFPA 13 2002 edition and we are in the 2016 edition
Plans shall show that a voice evac fire alarm system is required and shall be a separate permit obtained from TFD
Notes shall state: Owner shall obtain an operational permit from TFD for places of assembly.

Questions:

Jennifer Peel-Davis
Jennifer.Peel-Davis@Tucsonaz.gov
520-837-7033
Fire Plans Examiner
Tucson Fire Department