Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Permit Number - T22CM05581
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/29/2022 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 07/29/2022 | SSHIELD1 | ENGINEERING | REVIEW | Passed | |
| 08/01/2022 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | 1. Show a beam size with appropriate load carrying capacity where walls are removed, R301.1. 2. Show two or more 2O AMP small appliance circuits at the kitchen countertop receptacle outlets; they may also serve the breakfast room and dining room, but not other locations, E3703.2 and E3901.3. GFCI protected, E3902.6. Mark any existing receptacle outlets as (E) existing. |
| 08/12/2022 | AWARNER1 | NPPO | REVIEW | Passed |