Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T22CM05568
Parcel: 117040260

Address:
520 E 4TH ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T22CM05568
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/28/2022 PAUL CAMARENA ZONING REVIEW Reqs Change FROM: Paul Camarena
PDSD Zoning Review Section

PROJECT: T22CM05568
Addition
520 E 4TH ST Zoning HR-2

TRANSMITTAL DATE:?July 28, 2022


COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


This site is located in the HR-2 zone (UDC 4.7.9). Historic Review is required. Below is the link for the historic application. Please contact Jodie Brown (jodie.brown@tucsonaz.gov) or Michael Taku (michael.taku@tucsonaz.gov). Zoning can not approve until the historic review has been approved.

https://www.tucsonaz.gov/files/pdsd/Preservation/HPZ_Review_Application_Package_2020.pdf


1.COMMENT: Please provide all setback measurement for the breezeway addition

2.COMMENT: Draw dimension and label the height of the new structure measured from design grade to top of wall.


COMMENT: After researching PRO there are records for an expired addition T12CM08012, there are outstanding inspections. The permit referenced above must be finalized prior to zoning approval. The link provided below is the permit extension request form
https://docs.tucsonaz.gov/Forms/PDSD-Permit-Extension-Request-Form




If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov
07/28/2022 PCAMARE1 ENGINEERING REVIEW Passed
08/01/2022 AWARNER1 NPPO REVIEW Passed
08/12/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM05568

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
Please provide the following, at a minimum:
1. Fully dimensioned floor plans;
2. Window and door schedules;
3. Architectural and structural details sufficient to determine compliance of building elements with life safety requirements of the 2018 IRC;
4. Information on fenestration and building envelope insulation sufficient to determine compliance with the energy provisions of the 2018 IRC (or acknowledgement of exemption due to the historic nature of this building);
5. Structural plans and details, e.g.:
i. Foundation drawings
ii. Wall construction details, including wall bracing locations and methods
iii. Roof/ceiling framing plan and details
6. MEP plans and details, fixture and equipment schedules, electrical load information and panel schedules;
7. Electrical service riser diagram.


BUILDING REVIEW COMMENTS:
DeniedSubmitted drawings are insufficient in scope, dimension and detail to perform a review for the purpose of determining compliance with the jurisdiction’s adopted building, structural, plumbing, mechanical and electrical codes.
Please provide the following, at a minimum:
1. Fully dimensioned floor plans;
2. Window and door schedules;
3. Architectural and structural details sufficient to determine compliance of building elements with life safety requirements of the 2018 IRC;
4. Information on fenestration and building envelope insulation sufficient to determine compliance with the energy provisions of the 2018 IRC (or acknowledgement of exemption due to the historic nature of this building);
5. Structural plans and details, e.g.:
i. Foundation drawings
ii. Wall construction details, including wall bracing locations and methods
iii. Roof/ceiling framing plan and details
6. MEP plans and details, fixture and equipment schedules, electrical load information and panel schedules;
7. Electrical service riser diagram.


MECHANICAL REVIEW COMMENTS:
Denied
Submitted drawings are insufficient in scope, dimension and detail to perform a review for the purpose of determining compliance with the jurisdiction’s adopted building, structural, plumbing, mechanical and electrical codes.
Please provide the following, at a minimum:
1. Fully dimensioned floor plans;
2. Window and door schedules;
3. Architectural and structural details sufficient to determine compliance of building elements with life safety requirements of the 2018 IRC;
4. Information on fenestration and building envelope insulation sufficient to determine compliance with the energy provisions of the 2018 IRC (or acknowledgement of exemption due to the historic nature of this building);
5. Structural plans and details, e.g.:
i. Foundation drawings
ii. Wall construction details, including wall bracing locations and methods
iii. Roof/ceiling framing plan and details
6. MEP plans and details, fixture and equipment schedules, electrical load information and panel schedules;
7. Electrical service riser diagram.


ELECTRICAL REVIEW COMMENTS
Denied
Submitted drawings are insufficient in scope, dimension and detail to perform a review for the purpose of determining compliance with the jurisdiction’s adopted building, structural, plumbing, mechanical and electrical codes.
Please provide the following, at a minimum:
1. Fully dimensioned floor plans;
2. Window and door schedules;
3. Architectural and structural details sufficient to determine compliance of building elements with life safety requirements of the 2018 IRC;
4. Information on fenestration and building envelope insulation sufficient to determine compliance with the energy provisions of the 2018 IRC (or acknowledgement of exemption due to the historic nature of this building);
5. Structural plans and details, e.g.:
i. Foundation drawings
ii. Wall construction details, including wall bracing locations and methods
iii. Roof/ceiling framing plan and details
6. MEP plans and details, fixture and equipment schedules, electrical load information and panel schedules;
7. Electrical service riser diagram


PLUMBING REVIEW COMMENTS:
Denied
Please provide the following, at a minimum:
1. Fully dimensioned floor plans;
2. Window and door schedules;
3. Architectural and structural details sufficient to determine compliance of building elements with life safety requirements of the 2018 IRC;
4. Information on fenestration and building envelope insulation sufficient to determine compliance with the energy provisions of the 2018 IRC (or acknowledgement of exemption due to the historic nature of this building);
5. Structural plans and details, e.g.:
i. Foundation drawings
ii. Wall construction details, including wall bracing locations and methods
iii. Roof/ceiling framing plan and details
6. MEP plans and details, fixture and equipment schedules, electrical load information and panel schedules;
7. Electrical service riser diagram.


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov