Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T22CM05565
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/22/2022 | RPARSON1 | OIP | REVIEW | Completed | |
| 07/30/2022 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Reqs Change | Activity Number: T22CM05565 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Denied 1. Provide a lag bolt connection up-lift calculation demonstrating the wind load supporting capability. Note wind speed adopted is 115 MPH. R301.1 BUILDING REVIEW COMMENTS: Approved Installation of new PV system with 25 modules and associated equipment. Approved. MECHANICAL REVIEW COMMENTS: N/A ELECTRICAL REVIEW COMMENTS Denied 1. Provide manufacturer specification sheets for collector panels, inverters, and mounting hardware showing performance ratings and testing agencies. R106.1.1 PLUMBING REVIEW COMMENTS: N/A If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/31/2022 | NGARCIA3 | OUT TO CUSTOMER | Completed |