Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T22CM05555
Parcel: 116193160

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T22CM05555
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/30/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM05555


GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Denied
1. Indicate the type of building construction in the code data section on sheet a0.2. 2018 IBC table 601.
2. Update the drawing title for sheet a0.2 that indicates this is the “code floor plan for 2 thru 9”, only the common lobby floor is shown.
3. Include the storage and other area of the floor in the occupancy count for the required egress for the floor as a whole, not just the individual rooms. Indicate the total occupant load for the floor and its required cumulative exiting per 2018 IBC 1004.4. include the number of required exits, widths and indicate which exits are accessible on the drawings. 2018 IBC 1005,1006
4. The storage area is being modified and the path of egress is being altered by the addition of the new door in the previously open corridor. Indicate the exit path for this area as well.
5. Indicate the location of the exit signage and the emergency lighting with battery backup on the exiting plan sheet a0.2. Include the location of the existing emergency light outside of the egress doors per 1008.3.2. Coordinate the locations with the reflected ceiling and electrical plans.
6. Indicate the fire separation of one hour (sprinklered) will be maintained between the remodeled floor and the residences above. 2018 IBC Table 508.4.
7. Provide information on the existing wall construction that was previously the back of a storage units and is now the wall in the workroom/ break area/ toilet room. Verify that it is a 1 hour rated wall per 2018 IBC Table 508.4.
8. Note on the finish schedules sheet A3.2 that all newly installed interior finishes shall be rated a minimum of a class B (flame spread index 26-75, smoke developed index 0-450) in compliance with table 803.13 for A-3 occupancy.


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
Approved/subject to field approval


ELECTRICAL REVIEW COMMENTS
Conditionally Approved
E3.0 ELECTRICAL LIGHTING PLAN: Could not locate Keyed Note #4 (Photocell)


PLUMBING REVIEW COMMENTS:
Denied
First Plumbing Review:
1). Breakroom #103 appears to have the same sink as Kitchenette #113, but no plumbing is illustrated to the breakroom? - IPC 301.3, 602.1
2). Where is the required existing service sink located? show location. -IPC 403.1
3). Do any of the other lounges or cafe have plumbing fixtures or appliances that are missing plumbing illustrations? -IPC 106.3.1
4). This occupancy load of 193 requires 3 mens toilets & lavs and 3 womens toilets & Lavs.. -IPC 403.1


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
08/04/2022 WBERGER1 ENGINEERING REVIEW Passed
08/04/2022 WBERGER1 ZONING REVIEW Reqs Change RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Please resubmit updated drawings along with a detailed comment response letter, which states how all zoning review comments were addressed.

1. COMMENT: Keynote 10 on Sheet a2.1 is proposing the removal of the existing front entry doors and adjacent glazing. This parcel is located within the Rio Nuevo Area (UDC 5.12.7). Design Review Board approval is required prior to Zoning approval of this tenant improvement. Contact Maria.Gayosso@tucsonaz.gov for more information regarding Rio Nuevo and the Design Review Board.

If you have any questions about this transmittal, contact Wyatt Berger at Wyatt.Berger@tucsonaz.gov.
08/04/2022 WBERGER1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
08/19/2022 JVINCEN1 FIRE REVIEW Reqs Change Resolve building comments

john.vincent@tucsonaz.gov
5203495581
08/22/2022 ROBERT SHERRY WATER REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
08/23/2022 VVERA1 OUT TO CUSTOMER Completed