Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T22CM05554
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/08/2022 | SSHIELD1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
08/08/2022 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1 and C502.2.3, IECC 2018. 2. Show that the specified heat pump for the addition complies with the requirements of Section C403, IECC 2018. Reference: Section C502.2.3, IECC 2018. |
08/08/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
08/08/2022 | SSHIELD1 | ENGINEERING | REVIEW | Passed | |
08/08/2022 | ROBERT SHERRY | WATER | REVIEW | Completed | |
08/15/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
08/18/2022 | JVINCEN1 | FIRE | REVIEW | Approved | |
08/23/2022 | WILDAN | BUILDING-COMMERCIAL | REVIEW | Completed | |
08/29/2022 | STEVE SHIELDS | ZONING | REVIEW | Approved |