Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T22CM05527
Review Name: OTHER
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/23/2022 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Completed | |
09/30/2022 | ARUIZ1 | OIP | REVIEW | Reqs Change | COMMENT: It appears we have 2 permits in review for 522 and 526 N Norris. The plans attached to each permit do not match, in fact the panel layout differs on each. Please specify and label address for solar project. COMMENT: If applicable at resubmittal: Since the panels are going to be placed on two separate structures and one service shall continue to serve both structures, it is essential that all equipment and systems can be easily isolated at each building. Demonstrate how the equipment is going to be isolated by each structure. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
09/30/2022 | NGARCIA3 | OUT TO CUSTOMER | Completed |