Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T22CM05480
Parcel: 136201070

Address:
3411 S NAYASA AV

Review Status: Completed

Review Details: OTHER

Permit Number - T22CM05480
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/19/2022 RPARSON1 OIP REVIEW Completed
07/23/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Approv-Cond Activity Number: T22CM05480

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Conditionally Approved
Building Solar Project


BUILDING REVIEW COMMENTS:
Conditionally Approved
Building Solar Project


MECHANICAL REVIEW COMMENTS:
N/A

ELECTRICAL REVIEW COMMENTS
Conditionally Approved
Building Solar Project


PLUMBING REVIEW COMMENTS:
N/A

If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
07/25/2022 NGARCIA3 OUT TO CUSTOMER Completed