Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T22CM05467
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/04/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Specify that all proposed plumbing fixtures shall be listed by a third-party certification agency as complying with the relevant standards. Reference: Section 303.4, IPC 2018. |
| 08/04/2022 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Specify the exhaust fans for the bathrooms. Provide a minimum exhaust flow rate of 20 CFM if the exhaust is continuous, 50 CFM if the exhaust is intermittent in each bathroom. Reference: Section 403.3.2.3 and Table 403.3.2.3, IMC 2018. |
| 08/04/2022 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Verify that the water service to the building has a reduced pressure backflow prevention assembly installed after the water meter. Reduced pressure backflow prevention assemblies are required at the water meter for licensed, personal care facilities. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf |
| 08/08/2022 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 08/08/2022 | SSHIELD1 | ENGINEERING | REVIEW | Passed | |
| 08/08/2022 | SSHIELD1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 08/11/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please provide electrical plans that show branch circuit and panel designations and panel schedule. Also show breaker panel location. Provide a written response. Ref; 2018 IBC sec 107.2.1, 2017 NEC. City of Tucson Commercial Plan Submittal Requirements |
| 08/13/2022 | WILDAN | BUILDING-COMMERCIAL | REVIEW | Reqs Change | Activity Number: T22CM05467 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. Denied Sheet 1 Provide Building Type. Provide Occupancy Type. Provide Occupancy Load. Provide Exiting Plan. Sheet 1 Provide comment letter response to all items noted. Additional comments may follow when requested information is provided. Sheet 2 Provide Structural Engineering for Masonry openings and demolition. Provide complete framing plan for new walls and doors ways. Provide path of travel to the public way per IBC and ADAAG. Provide exit signs per the IBC. Provide slab repair details for plumbing trenches. Sheet 5 Provide complete details of bathroom regarding ADA. per ADAAG If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |
| 08/15/2022 | JPEELDA1 | FIRE | REVIEW | Reqs Change | Plans shall show the occupancy type and load. Plans shall show that a fire sprinkler and possibly a fire alarm system are required Plans shall show that the owner shall obtain an operational permit from TFD for a State Licensed Facility Questions: Jennifer Peel-Davis Jennifer.Peel-Davis@Tucsonaz.gov 520-837-7033 Fire Plans Examiner |