Review Date Reviewer's Name Type of Review Description Status Comments
08/15/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

Ref; Plan sheet E1.

1 Indicate fuse types and ratings for the service disconnects.

2 The Line diagram shows panel ‘RVP’ rated at 200 amps (Keynote #13) and the panel schedule shows a 400 amp rated panel. Please clarify.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.