| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/15/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comments and provide a written response. Ref; Plan sheet E1. 1 Indicate fuse types and ratings for the service disconnects. 2 The Line diagram shows panel ‘RVP’ rated at 200 amps (Keynote #13) and the panel schedule shows a 400 amp rated panel. Please clarify. Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. |