Permit Number: T22CM05457
Parcel: 125091080

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T22CM05457
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/28/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM05457

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
1. Provide all structural calculations for the installation of the HVAC systems


BUILDING REVIEW COMMENTS:
Denied
1. The egress plan provided is incomplete and missing information. Provide a very thorough egress plan, that indicates travel distances, egress signage, exit separation, the location of all equipment and tables, and all other required information.
2. The ramp indicated on the egress plan as a means of egress and accessible path appears to be non-compliant. Provide ramp details that show evidence of compliance with Section 1012 of the IBC and Section 405 of ANSI A117.1
3. The accessibly plan is incomplete. Clearly show the the location of all tables and equipment and indicate the clear floors spaces for traveling throughout the space.
4. At least 5% of the dining surfaces are required to have mobility features. Provide calculations of the required amount of accessible seating and indicate the locations. Additionally, ensure that surfaces are properly dispersed throughout the structure. Section 226.1 and 226.2 of the 2010 ADAAG.
5. Provide a Building Code Data Legend on the Title Sheet. Include the following code information for each building proposed:
• Occupancy Classification(s)
• For Mixed Occupancy Buildings, state whether the “non-separated” or “separated” option was chosen from Sections 508.3 / 508.4.
• Description of Use
• Type of Construction
• Sprinklers:
• Stories
• Height
• Floor Area
• Occupant Load
• Justification to exceed allowable area in Table 503 (if applicable)
• Justification to exceed allowable height or stories in Table 503 (if applicable)
1. The construction type listed on the cover page is incorrect. Provide a corrected construction type. VA or VB.
2. Provide plumbing fixture requirement calculations.
3. Provide a room finish schedule in accordance with Chapter 8.
4. Provide all accessibility details.
5. Provide an enlarged bathroom plan that shows all dimensions and clear floor spaces.
6. Provide a complete list of adopted and applicable building codes.


MECHANICAL REVIEW COMMENTS:
Denied
1. Please provide a COMcheck that indicates compliance for new mechanical system and scan that data onto one of the mechanical sheets. This provides evidence the mechanical system is in compliance.
2. With a Type I exhaust hood being present, an air balance schedule will be required. Provide an air balance schedule.


ELECTRICAL REVIEW COMMENTS
Denied
1. The electrical floor plan provided is completely different that the proposed floor plan. Provide a correct electrical floor plan and correlate all applicable requirements.


PLUMBING REVIEW COMMENTS:
Denied
1. There are several sinks and floor sinks that will handle grease laden wastes that are not connected to the grease interceptor. Connect all sinks that will handle grease laden wastes to the grease interceptor. Additionally, update the grease interceptor sizing calculations.


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
08/09/2022 ROBERT SHERRY WATER REVIEW Completed
08/12/2022 IMONSHI1 ZONING REVIEW Reqs Change FROM: Iman Monshizadeh

PDSD Zoning Review Section

PROJECT: T22CM05457 – Zemams Resturant

Building Plan Review (1st Review)

2731 E Broadway Bl / C-1

TRANSMITTAL DATE: 8/12/2022



COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed

1.COMMENT: Zoning has reviewed the building plans for compliance with the associated Development Package DP22-0181. Zoning cannot approve the building plans until the DP is approved.

If you have any questions about this transmittal, Contact Iman Monshizadeh at (520) 837-4082 or by email Iman.Monshizadeh@tucsonaz.gov
08/12/2022 IMONSHI1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Reqs Change Impact fees will be assesed once zoning review is complete
08/15/2022 JVINCEN1 FIRE REVIEW Reqs Change Resolve building comments

john.vincent@tucsonaz.gov
5203495581
08/16/2022 SSHIELD1 ENGINEERING REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
08/16/2022 VVERA1 OUT TO CUSTOMER Completed