Review Date Reviewer's Name Type of Review Description Status Comments
07/28/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM05446

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied1. Provide all structural calculations for the installation of the HVAC systems.


BUILDING REVIEW COMMENTS:
Denied
1. The egress plan provided is incomplete and missing information. Provide a very thorough egress plan, that indicates travel distances, egress signage, exit separation, the location of all equipment and tables, and all other required information.
2. The accessibly plan is incomplete. Clearly show the the location of all tables and equipment and indicate the clear floors spaces for traveling throughout the space.
3. At least 5% of the dining surfaces are required to have mobility features. Provide calculations of the required amount of accessible seating and indicate the locations. Additionally, ensure that surfaces are properly dispersed throughout the structure. Section 226.1 and 226.2 of the 2010 ADAAG.
4. Provide a Building Code Data Legend on the Title Sheet. Include the following code information for each building proposed:
• Occupancy Classification(s)
• For Mixed Occupancy Buildings, state whether the “non-separated” or “separated” option was chosen from Sections 508.3 / 508.4.
• Description of Use
• Type of Construction
• Sprinklers:
• Stories
• Height
• Floor Area
• Occupant Load
• Justification to exceed allowable area in Table 503 (if applicable)
• Justification to exceed allowable height or stories in Table 503 (if applicable)
1. The construction type listed on the cover page is incorrect. Provide a corrected construction type.
2. Provide plumbing fixture requirement calculations.
3. Provide a room finish schedule in accordance with Chapter 8.
4. Provide all accessibility details.
5. Provide an enlarged bathroom plan that shows all dimensions and clear floor spaces.
6. Provide a complete list of adopted and applicable building codes.


MECHANICAL REVIEW COMMENTS:
Denied
1. Please provide a COMcheck that indicates compliance for new mechanical system and scan that data onto one of the mechanical sheets. This provides evidence the mechanical system is in compliance.
2. Provide a narrative as to what type of cooking will be present and it's relation to the hood requirements.


ELECTRICAL REVIEW COMMENTS
Denied
1. No egress illumination provided. Provide a sufficient amount of egress illuminations in accordance with Section 1008.


PLUMBING REVIEW COMMENTS:
Denied
1. Provide the location of required grease interceptors that may be required. Provide al necessary details and sizing calculations.


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
08/09/2022 SCABRAL1 ENGINEERING REVIEW Reqs Change The CM cannot be approved until the DP22-0181 is approved.
08/09/2022 ROBERT SHERRY WATER REVIEW Completed
08/15/2022 JVINCEN1 FIRE REVIEW Reqs Change Resolve building comments

john.vincent@tucsonaz.gov
5203495581
08/24/2022 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: T22CM05446 – DP22-0181
5602 E Broadway Blvd. – C-1
TI Zeman’s Lounge – (1st Review)

TRANSMITTAL: August 24, 2022

This site is located in C-1 Zone (UDC Article 4.7.20) Food Service w/alcoholic beverage service as an accessory use. (UDC Table 4.8-4), subject to Use Specific Standards 4.9.4.M.1 & 5, 4.9.13.O, 4.9.4.V.1, 3, & 5-9, 4.9.4.C.3, and 4.9.13.O are met.

1. As DP22-0181 has not completed the first review Zoning is not able to compare the building plans to the DP. Once the 1st review of the DP is completed and comments addressed Zoning will review the building plans for compliance with the DP. Additional comments maybe forth coming. Zoning cannot approve the building plans until the DP is approved by all review agencies.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
08/24/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
08/24/2022 NGARCIA3 OUT TO CUSTOMER Completed