Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Permit Number - T22CM05441
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/27/2022 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | ZONING REVIEW TRANSMITTAL FROM: PDSD Zoning Review PROJECT: T22CM05441 7438 E 29th St - R-1 Detached Porch Structures (1st Review) TRANSMITTAL: July 27, 2022 This site is located in the R-1 zone (UDC 4.7.8). A single-family residence is a permitted use in this zone (Table 4.8-2) subject to Use Specific Standards 4.9.7.B.5 – 9. 1. Based on aerial photos there is a porch structure along the southeast side of the existing SFR not shown on the plan. Zoning was not able to find approved permits for this structure. Provide approved permit documents with your next submittal or include this structure with this permit. Another option is to remove this structure from the site. If you elect to remove this structure show it on the plan to be removed. 2. Provide setback dimensions from all structures to the applicable property lines. Setbacks for the porch structures are measured from the post supporting the structure as long as the roof overhang does not exceed 2’-0” If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov. |
| 07/27/2022 | SSHIELD1 | ENGINEERING | REVIEW | Passed | |
| 07/27/2022 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | A roof overhang may not extend closer than 24" to the neighboring property line. Any part of a roof projection extending into the 3-foot fire separation distance from the property line requires not less than one-hour fire-resistive construction on the underside, R302.1 (City of Tucson Amended). Either provide a complete wall barrier with not less than one-hour fire-resistive construction in compliance with IBC Table 721.1(2) or remove the portion of structure within 3 feet to the property line. |
| 08/15/2022 | AWARNER1 | NPPO | REVIEW | Approved |