Permit Number: T22CM05420
Parcel: 10609044A

Address:
1440 W PRINCE RD

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T22CM05420
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/04/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response

1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered Electrical design professional. Provide complete electrical plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. Ref; 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements
08/08/2022 SSHIELD1 ENGINEERING REVIEW Passed
08/08/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/08/2022 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: T22CM05420
1440 W Prince Rd – C-2
Temporary Power for Construction Trailer – (1st Review)

TRANSMITTAL: August 8, 2022

This site is located in C-1 Zone (UDC Article 4.7.21)

1. A Temporary Use Permit (TUP) is required for this project, see requirements found at: https://www.tucsonaz.gov/pdsd/all-application-forms-submittal-requirements. Contact for the TUP is Mark Castro, Mark.Castro@tucsonaz.gov.

2. The proposed construction trailer shall be shown on the approved Development Package (DP) for this site. Zoning was not able to find a DP for this site. Provide the DP case number with the next submittal.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
08/09/2022 JVINCEN1 FIRE REVIEW Approved
08/26/2022 WILDAN BUILDING-COMMERCIAL REVIEW Reqs Change Activity Number: T22CM05420

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

BUILDING REVIEW COMMENTS:
Denied
Plan sheet is required to be sealed by a professional registrant per ASRS 32-125 and City of Tucson Commercial plan submittal requirements.



If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
08/26/2022 VVERA1 OUT TO CUSTOMER Completed