Permit Number: T22CM05418
Parcel: 136082340

Address:
9571 E 33RD ST

Review Status: Completed

Review Details: OTHER

Permit Number - T22CM05418
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/18/2022 RPARSON1 OIP REVIEW Completed
07/25/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM05418

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved
Calculations for loads accepted


BUILDING REVIEW COMMENTS:
Approved
Installation of New PV system with 19 modules and associated equipment. Approved


MECHANICAL REVIEW COMMENTS:
N/A


ELECTRICAL REVIEW COMMENTS
Denied
1. Noted that the line side tap will negate the use of the main breaker as the initiation of Rapid shutdown operation. Please clarify the location of the Rapid shutdown initiation.
2. There is no load side backfeed breaker please remove reference to PV Solar Breaker on Main Service panel.


PLUMBING REVIEW COMMENTS:
Approved


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
07/25/2022 NGARCIA3 OUT TO CUSTOMER Completed