Permit Number - T22CM05416
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/18/2022 | RPARSON1 | OIP | REVIEW | Completed | |
| 07/22/2022 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Reqs Change | Activity Number: T22CM05416 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Denied Sheet PV 1.0 – Show fire setback and fire pathway per 2018 IRC section R324.6. System legend identifies “FIRE SETBACK AND FIRE PATHWAY” yet it is missing from site plan 1/PV 1.0. BUILDING REVIEW COMMENTS: Denied Sheet PV 1.0 – Show fire setback and fire pathway per 2018 IRC section R324.6. System legend identifies “FIRE SETBACK AND FIRE PATHWAY” yet it is missing from site plan 1/PV 1.0. MECHANICAL REVIEW COMMENTS: N/A ELECTRICAL REVIEW COMMENTS Denied Sheet PV 1.0 – Show fire setback and fire pathway per 2018 IRC section R324.6. System legend identifies “FIRE SETBACK AND FIRE PATHWAY” yet it is missing from site plan 1/PV 1.0. PLUMBING REVIEW COMMENTS: N/A If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/22/2022 | NGARCIA3 | OUT TO CUSTOMER | Completed |