Permit Number: T22CM05391
Parcel: 134020250

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T22CM05391
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/26/2022 STEVE SHIELDS ZONING REVIEW Reqs Change FROM: PDSD Zoning Review Section

PROJECT: T22CM05391
4212 E PASEO GRANDE - RX-1
Accessor Structure (1st Review)

TRANSMITTAL DATE: July 26, 2022

COMMENTS: Please resubmit revised drawings and any a detailed response letter, which states how all Zoning Review Section comments were addressed.

1. Per UDC Article 6.6.2.B An accessory building shall be built only on a lot occupied by a principal building or use. The proposed metal building is not allowed on a lot by itself. A Board of Adjustment for Variance is required.

2. Per UDC Article 6.6.3.D Accessory structures, except for accessory dwelling units, shall not exceed 12 feet in height, unless attached to a principal structure. The proposed structure exceeds the allowed height. A Board of Adjustment for Variance is required.

3. The adjacent zoning listed for the north and south properties is not correct.

Board of Adjustment application/requirements can be found at: https://www.tucsonaz.gov/files/pdsd/codes/Zoning_Administration_Application_BA_fillable.pdf. The Board of Adjustment is a separate submittal from this building plan and is submitted at: https://www.tucsonaz.gov/pdsd-filedrop, using the Submission Type “Zoning Administration”. Contact of the Board of Adjustment is Mark Castro at Mark.Castro@tucsonaz.gov.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
07/26/2022 SSHIELD1 ENGINEERING REVIEW Passed
07/27/2022 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change Update the code reference on sheet C1 to 2018 IBC and 2018 IEEC. The 2018 IRC is intended for dwelling requirements. The plans show a storage building (without utilities) on undeveloped property. Also, the 2012 IEEC is outdated.
08/15/2022 AWARNER1 NPPO REVIEW Needs Review CDRC TRANSMITTAL

PROJECT:
ACTIVITY NO. T22CM05391
ADDRESS/PARCEL: 9151 E Magdalena Rd
ZONING: RX-1

7.7. Native Plant Preservation
The NPPO is intended to encourage preservation in place of healthy native plants through sensitive site design that minimizes the disruption of areas within the site containing healthy plants while allowing for salvage and transplanting plants on the site that are likely to survive.
A Native Plant Preservation Plan, Section 7.7.4, is required to be submitted and approved or a request for an exception from the Native Plant Preservation requirements approved in accordance with Sections 7.7.3.D.3 & .4 of the Unified Development Code (UDC) and Admin. Manual Section 2-11.0.0 prior to Grading Plan approval. Please note that Mesquite hybrids will be considered native trees and should be included in NPP inventory.

By far, the easiest way to meet this requirement is to set aside 30% of the lot for Natural Undisturbed Open Space (NUOS).

An Environmental Resource Report is required for any regulatory washes on site.

If you have any questions about this transmittal, contact Anne Warner, RLA
PDSD Landscape/NPPO Review at email anne.warner@tucsonaz.gov