Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T22CM05357
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/02/2022 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | ZONING REVIEW TRANSMITTAL FROM: PDSD Zoning Review PROJECT: T22CM05357 616 n 4the Ave – C-3 Patio Expansion (1st Review) TRANSMITTAL: August 2, 2022 This site is located in C-3 Zone (UDC 4.7.22), Alcoholic Beverage Service, Excluding a Large Bar is an allowed use in the zone (UDC TABLE 4.8-4: PERMITTED USES - COMMERCIAL AND MIXED USE ZONES). 1. Per UDC Article 3.3.3.G.2.c A site plan (Development Package) is required for the following types of development: Existing development undergoing a change of use, building structure additions, and/or a reconfiguration of an area outside a building. A development package (DP) meeting the requirements of Administrative Manual (AM) 2-06 must be submitted and approved prior to approval of this building plan. The DP is a separate submittal from the building plans and is submitted at: https://docs.tucsonaz.gov/Forms/tucsonpermitapp, using Submission Type “Site Review”. Either provide approved permit documents for the patio areas with the next submittal or submit a DP. The DP will need to be approved prior to approval of this building permit. If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov. |
| 08/02/2022 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 08/02/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comments and provide a written response. Ref; Plan Sheets A-9, A-9.1. 1 Include all new or replaced luminaires in the Lighting Schedule, interior and exterior. 2 Include existing electrical building loads in the load calculations and show total building load. 3 Show the electrical service size in Volts, Phase, Amps, AIC rating. Panels also. 4 Show the OCPD feeding the new panel ‘C’ in the panel ‘B’ schedule. 5 Provide plans and evidence on the plans that the proposed exterior lighting fully complies with the Outdoor Lighting Code. See section 104 for plan submittal requirements. Provide site lighting plans with the following information on the plans; Provide a complete luminaire schedule. Size of the parcel in acres. Not just the building footprint. (.28 acres) per site plan ‘A-1’ not .39. See table 401.1, lighting area and option and indicate this information in the lighting site plan, also showing the locations and types of all exterior luminaires including existing. 402.1 (light source color temperature requirements), shielding requirements, etc . Provide calcs for total lumens allowed and total lumens proposed per acre including existing, for Full Cut Off and Unshielded per table 401.1. Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2. Specify any exceptions used. Curfew lighting controls If applicable. (6 hours standby power) section 403.5. Do not confuse the Outdoor Lighting Code with the IECC. Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. 2012 Tucson/Pima County Outdoor Lighting Code |
| 08/02/2022 | SSHIELD1 | ENGINEERING | REVIEW | Passed | |
| 08/02/2022 | SSHIELD1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 08/09/2022 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 08/09/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 08/15/2022 | JPEELDA1 | FIRE | REVIEW | Reqs Change | Plans shall show that the building needs to have a fire sprinkler system installed and a fire alarm system. Questions: Jennifer Peel-Davis Jennifer.Peel-Davis@Tucsonaz.gov 520-837-7033 Fire Plans Examiner Tucson Fire Department |
| 08/19/2022 | WILDAN | BUILDING-COMMERCIAL | REVIEW | Reqs Change | Activity Number: T22CM05357 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. Sheet A-1 Show enlarged site plan with accessible path of travel to parking to the public way per ADAAG. Sheet A-4 Verify Paver's meet requirements of ADAAG. Provide documentation. Sheet A6 Show detail of Gate Hardware to comply with ADAAG. If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |