Permit Number: T22CM05354
Parcel: 125101390

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T22CM05354
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/22/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM05354

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Denied
1. No egress plan provided. Provide a thorough egress plan.
2. The occupancy classifications for the boba tea is incorrect. Provide a correctly classified tenant space and correlate all applicable requirements.
3. It appears that the proposed business plan is two separate tenants. In accordance with Section 2902.3 of the IBC employee restrooms required and would not be abled to be shared by the tenants. Provide clarification.
4. Provide evidence of compliance that all interior finishes comply with Chapter 8.
5. An insufficient amount of exit signage is provided. Provide the correct amount of exit signage in accordance with Section 1013.


MECHANICAL REVIEW COMMENTS:
Denied
1. Source capture is required at each pedicure station of exhausting not less than 50 cfm per station. Provide proper exhausting at each pedicure station.
2. Mechanical exhaust and recirculation of air is not permitted in nail salon in accordance with sub note b of table 403.3.1.1 of the IMC


ELECTRICAL REVIEW COMMENTS
Denied1. The location of egress illumination is not indicated on the electrical plan. Provide the location of all egress illumination in accordance with Section 1008

PLUMBING REVIEW COMMENTS:
Approved

If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
08/02/2022 SSHIELD1 ENGINEERING REVIEW Passed
08/02/2022 STEVE SHIELDS ZONING REVIEW Approved
08/02/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/10/2022 ROBERT SHERRY WATER REVIEW Completed
08/18/2022 JVINCEN1 FIRE REVIEW Reqs Change Resolve building comments