Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T22CM05349
Parcel: 11011364A

Address:
4707 E GRANT RD

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T22CM05349
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/01/2022 PCAMARE1 ENGINEERING REVIEW Passed
08/01/2022 PAUL CAMARENA ZONING REVIEW Approved
08/01/2022 PCAMARE1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/05/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM05349

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved

BUILDING REVIEW COMMENTS:
Approved

MECHANICAL REVIEW COMMENTS:
Denied
1.Return or air transfer grill shall not be located in men's bathroom sheet M101 (IMC2018,601.5
2. This supply is connected to the return duct but it has a supply diffuser symbol in both officesplease correct on sheet M101 for AC-6
3. Provide return air to flex room #108 you have 2 supply diffusers please correct sheet M101 (IMC2018,601.5)
4. A conference room 845 square feet will have 42 people not 18 and according the ventilation calculations you need 327 cfm of outside air to the conference room not 229 cfm your missing the breakroom, flex room, collab room etc. please correct your ventilation table calculations sheet M401 (IMC2018,403.3.1.1.1)
5. Provide gas pipe riser plan showing the 1. furthest gas run from the meter to the furthest appliance 2. the total gas load in cfh 3. the gas inlet pressure and 4. the pressure drop and 5. the table in the IFGC used to size the gas pipe sheet M2.1

ELECTRICAL REVIEW COMMENTS
Approved

PLUMBING REVIEW COMMENTS:
Denied
First Plumbing Review:
1). Add fixture side wall clearances to plan page A401- IPC 404.2, 405.3.1
2). Existing water heater location on plan page P101 is more than 50ft from new lavatories, suggest add point of use water heater at each lav, see IPC 607.2
3). Sanitary & venting configuration not clear on P101, add sanitary/venting riser diagram -IPC 106.3.1
4). Add gas plan for the new rooftop AC units shown on plan pages M201 & M401. -IFGC 106.3.1



If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
08/10/2022 ROBERT SHERRY WATER REVIEW Completed
08/15/2022 JVINCEN1 FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/15/2022 VVERA1 OUT TO CUSTOMER Completed