Permit Number: T22CM05283
Parcel: 136326900

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T22CM05283
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/18/2022 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T22CM05283 R1

PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

PROVIDE A COMPLETE PLAN SET

Place each sheet into a single plan set. https://www.tucsonaz.gov/pdsd/residential-permits

SITE PLAN:

Provide the square footage of each altered space.

SECTIONS - DETAILS:

An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38 or R-30 when extended over the wall top plate for additions under 500 SF. A vented attic requires the opening size (area SF / 150).

ELECTRICAL PLANS:

Smoke alarms are required outside each separate sleeping area (both sides of entrance doors), R314.3.2.

If you have any questions, please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review
08/18/2022 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: T22CM05283
4879 S Placita Joropo
Additions and enclosures of residence (2nd Review)

TRANSMITTAL DATE: August 18, 2022

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1. This comment was not fully addressed. Provide a residential plot plan meeting that meets the requirements found at: https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf. The specific requirements are numbered and listed on the second page of the link provided.
a. Provide a lot coverage calculation that meets the requirements of UDC Article 6.4.3 and the example shown on the Residential Plot Plan Requirements on the plot plan.
b. Indicate the zoning of the property and all surrounding properties on the plot plan.
c. Provide the legal description “RANCHO CANCION WEST LOT 33” on the plot plan.

2. This comment was not fully addressed. Demonstrate how the required dustproofing is provided for the required parking space. Also, demonstrate how this parking space functions as there is a fence located in the same area. Provide a floor plan of the entire residence to demonstrate compliance with UDC 4.9.7.B.7. For any new single-family dwelling in the R-1 zone with five bedrooms, three parking spaces are required. For every bedroom over five, one additional space is required for each bedroom. For all single-family family dwellings in the R-1 zone with five or more bedrooms, all parking spaces must be located on-site, either in a side or rear perimeter yard. Parking spaces may not be located in a vehicular use area in any front street perimeter yard. A parking area is not required to be developed to a commercial standard. A dustproof parking surface is required to at least a minimum of two inches of compacted pea gravel. An existing covered residential parking area may be used.

3. Based on aerial photos there is a shed type structure located on the west and east side of the existing SFR, show these structures on the plan and include them in the lot coverage calculation.

4. The plans shall be submitted as a single multi-page pdf file.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.