Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T22CM05250
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/08/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comments and provide a written response. 1 The previous electrical plan review comment concerning the line side tap was not addressed. The photograph submitted for the line side tap reference shows switchgear equipment. The electrical plan shows a gutter and 2 service disconnects. Re visit the previous electrical plan review comment and provide the requested information in detail. Indicate in detail on the plans and re-submit. Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. |