Permit Number: T22CM05250
Parcel: 11619227A

Address:
255 N GRANADA AV

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T22CM05250
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/02/2022 PCAMARE1 ENGINEERING REVIEW Passed
08/02/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response
1. Provide more detail as to how the line side PV interconnection tap is going to be performed in the existing 200 amp service disconnect switch.

2. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered Electrical design professional. Provide complete electrical plans sealed by an Arizona Registrant. Ref; 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements
08/02/2022 PAUL CAMARENA ZONING REVIEW Approved
08/04/2022 PSHELTO1 FIRE REVIEW Approved
08/20/2022 WILDAN BUILDING-COMMERCIAL REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
08/22/2022 NGARCIA3 OUT TO CUSTOMER Completed